Skip to main content

Ideally, the splices are tested with an OTDR

Ideally, the splices are tested with an OTDR as soon as they are made and before placing them in a splice tray. The fusers give an estimate of the splice loss, but it is only an estimate. The OTDR can confirm the quality of the splices, giving the installer the assurance that the splice is good and that the splice box will not need to be reopened to redo a defective splice.   

Special care should be taken when putting the splices in the trays and when organizing the underground ducts or fibers in the box. A problem that arises a lot is that the fibers are broken when the trays and boxes are assembled. Finding the fiber breaks inside the box is complicated since they are too close to the joint to resolve them with an OTDR. If the joint is close enough to allow its location with a visual fault locator, the break can be found with a visual inspection. 


Termination

At least the termination is usually done inside a building near the telecommunications equipment, either a termination of a wiring of an installation in an external or internal plant. The installer may have trouble finding the right space, for example in a telecommunications room with rows of connection panels and racks.  With luck, the cable installer will have stored each of the service cables in a loop to take them to an open area and finish them. Many installers use portable folding tables or carts with wheels to create a work area where they can reach the ends of the cables.

If the building is still under construction, dust can be a problem. Even in finished buildings, air conditioning systems can lift dust. You must check that there is no dust; If it is necessary to work in a dusty environment, clean all tools, granulated sandpaper for polishing and connectors as often as necessary.

If they are single-mode cables that terminate with a connectorized fiber ( pigtail ) cable , follow the same precautions when locating splices or fibers in cable trays and boxes to avoid damage. For 900-micron multimode fibers of tight structure with direct termination in a distribution cable, you must leave a suitable length to store the leftover fibers and avoid tight curvatures as they can cause problems with fiber losses in the future.
Also Read : fiber splicing certification

As with the splices, each connector must be tested when the fiber termination is complete. Check each polished connector with a microscope to make sure the polish was successful. If possible, test each pre-polished connector with a visual fault locator. After both ends of the fiber are finished, point-to-point loss must be proven and everything documented. The connectors with a lot of loss must be terminated again and this saves the time of having to do it when the installer is ready in the work area.   

Comments

Popular posts from this blog

The most popular method and the method required in TIA-568

Choice of the reference method Some reference books and manuals show that to establish the reference power for loss, only a reference launch cable, launch and reception cable connected with a coupling adapter or even three reference cables is used.  In fact, industry standards include all three methods to establish a "0dB loss" reference.  The two or three-wire reference methods are acceptable for some tests and are the only way you can test some connectors, but it will reduce the loss you measure in the amount of loss between your reference wires when you set your "  You could start the test with faulty launch wires, which would cause all loss measurements to be incorrect.  This means that the inspection and testing of the reference cables are very important, in order to ensure that they are in good condition.  You could start the test with faulty launch wires, which would cause all loss measurements to be incorrect.  This means that the inspection and...

If we detect N photons from a coherent state of light for a measurement,

Short answer: A good order of magnitude rule of thumb for the maximum possible bandwidth of an optical fibre channel is about 1 petabit per second per optical mode. So a "single" mode fibre (fibre with one bound eigenfield) actually has in theory two such channels, one for each polarisation state of the bound eigenfield. I'll just concentrate on the theoretical capacity of a single, long-haul fibre; see roadrunner66's answer for discussion of the branching in an optical network. The fundamental limits always get down to a question of signal to noise in the measurement (i.e. demodulation by the receiver circuit). The one, fundamentally anavoidable, noise source on a fibre link is quantum shot noise, so I'll concentrate on that. Therefore, what follows will apply to a short fibre: other noise sources (such as Raman, amplified spontaneous emission from in-line optical amplifiers, Rayleigh scattering, Brillouin scattering) tend to become significant roughly in pro...

The cable types, the cable network hardware

The ways to build the OSP cables are specifically oriented to the strength of the cable, depending on whether they are buried directly or inside conductors, located underwater, or installed in the air on poles. The proper way for cable routing must be chosen. In some installations, several types of cable are even used. Having good construction plans can be useful when working with cable manufacturers to find the right types of cables and request sufficient quantities. You should always request more cable than is needed for the length of the path, in order to be able to store the service cable in the form of a loop, prepare the termination of the cable and save what you need in case it is necessary to Make a repair in the future. As well as the cable types, the cable network hardware types are very diverse and should be chosen in a way that is compatible with the cable types used. With so many hardware options, working with cable manufacturers is the most expeditious way to choose ha...